An Improved Protocol for Indoor Airborne Bacterial Enumeration and Elimination Using a Cold- Plasma Air Sanitizer: A pilot study

Authors

  • Mohammed Ibrahim Saeed Author
  • Ahmed Luay Osman Author
  • Abdelgadir Alamin Altoum Author
  • Salah-Eldin Omar Hussein Author
  • Salma Elnour Author

DOI:

https://doi.org/10.54878/r2x84577

Keywords:

Airborne-bacteria, Elemination, Bacterial-enumeration, Cold-Plamsa technology, Indoor-Air quality

Abstract

Airborne bacteria pose significant health risks in indoor environments, particularly for immunocompromised individuals. Air sanitizers represent a promising intervention for reducing microbial contamination in enclosed spaces. Objectives: This study evaluated the efficacy of a cold-plasma air sanitizer in reducing airborne bacterial contamination and developed a standardized protocol for bacterial enumeration in indoor air samples. Methods: Air samples (500 L per sample) were collected using a Sugold FX-100ST microbial air sampler (flow rate 100 L/min for 5 minutes) from microbiology and hematology teaching laboratories (1000 m³ room volume) at Gulf Medical University. Samples were collected immediately before sanitizer activation (baseline) and at 30-minute intervals during cold-plasma treatment (TPA Air Technology, Germany) for 24 hours. Samples were directly inoculated onto Chocolate agar, CLED agar, and Chromogenic UTI agar and incubated at 37°C for 24-48 hours. Total airborne particle counts (0.3-10 μm) were measured using an Atmotech particle counter. Experiments were performed in triplicate on three separate days (n=9 per time point). Bacterial identification was performed using Gram staining and biochemical tests. Statistical analysis employed paired t-tests and one-way ANOVA (p<0.05). Results: Significant bacterial reductions were observed following sanitizer activation. Baseline bacterial concentrations were 75.4±12.3 CFU/500L on Chocolate agar, 59.2±10.8 CFU/500L on CLED agar, and 26.4±6.7 CFU/500L on Chromogenic agar. Mean reduction rates at 24 hours were 94.7%, 96.5%, and 96.1%, respectively. Predominant organisms were Micrococcus spp. (62%) and Bacillus spp. (28%). Coagulase-positive Staphylococcus aureus (n=2) and Gram-negative species including Burkholderia cepacia and Stenotrophomonas maltophilia were also isolated. Strong positive correlation was observed between particle counts and bacterial concentrations (r=0.89, p<0.001). Conclusion: Cold-plasma air sanitization effectively reduced airborne bacteria by >90% within 24 hours. The standardized enumeration protocol developed in this study provides a simplified approach for indoor air quality assessment. Implementation of cold-plasma technology in healthcare settings could reduce respiratory infection risks for susceptible populations.

References

Hinds WC, Zhu Y. Aerosol technology: properties, behavior, and measurement of airborne particles. 3rd ed. Hoboken: John Wiley & Sons; 2022. 528 p.

World Health Organization. WHO global air quality guidelines: particulate matter (PM2.5 and PM10), ozone, nitrogen dioxide, sulfur dioxide and carbon monoxide. Geneva: World Health Organization; 2021. 273 p.

Zimlichman E, Henderson D, Tamir O, Franz C, Song P, Yamin CK, et al. Health care-associated infections: a meta-analysis of costs and financial impact on the US health care system. JAMA Intern Med. 2013;173(22):2039-46.

Thompson KA, Bennett AM. Healthcare environment: air quality. In: Batt CA, Tortorello ML, editors. Encyclopedia of food microbiology. 2nd ed. Oxford: Academic Press; 2014. p. 127-35.

Fabian P, McDevitt JJ, DeHaan WH, Fung ROP, Cowling BJ, Chan KH, et al. Influenza virus in human exhaled breath: an observational study. PLoS ONE. 2011;6(6):e21481.

Lin K, Marr LC, Li Y. Aerosol sampling and detection of airborne viruses. Environ Sci Technol. 2020;54(3):1583-91.

Prussin AJ, Schwake DO, Marr LC. Ten questions concerning the aerosolization and transmission of Legionella in the built environment. Build Environ. 2017;123:684-95.

Centers for Disease Control and Prevention. Guidelines for environmental infection control in health-care facilities. MMWR Recomm Rep. 2003;52(RR-10):1-42.

Gonzalez-Martin C. Airborne infectious microorganisms. In: Schmidt TM, editor. Encyclopedia of microbiology. 4th ed. Oxford: Academic Press; 2019. p. 52-69.

Myhrvold C, Freije CA, Gootenberg JS, Abudayyeh OO, Metsky HC, Durbin AF, et al. Field-deployable viral diagnostics using CRISPR-Cas13. Science. 2018;360(6387):444-8.

Jiang X, Wang R, Wang Y, Su X, Ying Y, Wang J. Advances in biosensors for airborne pathogen detection: a review. Biosens Bioelectron. 2022;198:113805.

World Health Organization. Laboratory testing for SARS-CoV-2: interim guidance. Geneva: World Health Organization; 2021. WHO/2019-nCoV/laboratory/2021.1.

Song L, Zhou J, Wang C, Meng G, Li Y, Jarin M, et al. Airborne pathogenic microorganisms and air cleaning technology development: a review. J Hazard Mater. 2022;424:127429.

Al-Abdallah AH, Al-Dakheel SA, Al-Abkari HA. Impact of air-conditioning filters on microbial growth and indoor air pollution. In: Low-temperature technologies. London: IntechOpen; 2019. p. 179-206.

Han L, Patil S, Boehm D, Milosavljević V, Cullen PJ, Bourke P. Mechanisms of inactivation by high-voltage atmospheric cold plasma differ for Escherichia coli and Staphylococcus aureus. Appl Environ Microbiol. 2016;82(2):450-8.

Chen Z, Liu Y, Li J, Wang X, Zhang H, Zhou R, et al. Cold plasma technology for air disinfection: recent advances and future perspectives. J Hazard Mater. 2023;456:131984.

Bisag A, Colombo V, Gherardi M, Laurita R, Liguori A, Santoro M, et al. Atmospheric pressure cold plasma for air purification. Environ Sci Technol. 2022;56(8):5121-33.

Szczotko M, Orych I, Maka Ł, Solecka J. A review of selected types of indoor air purifiers in terms of microbial air contamination reduction. Atmosphere. 2022;13(5):800.

Brincat JP, Sardella D, Muscat A, Decelis S, Grima JN, Valdramidis V, et al. A review of the state-of-the-art in air filtration technologies as may be applied to cold storage warehouses. Trends Food Sci Technol. 2016;50:175-85.

Stenström KE, Pédehontaa-Hiaa G, Ramljak B, Rääf C. Alpha spectrometry of radioactive aerosols from the European Spallation Source: an investigation of the possibilities of direct alpha spectrometry. Radiat Meas. 2024;172:107089.

Joppolo CM, Gandini J. Emerging technologies for air cleaning and their integration in HVAC systems: which role in the increasing quest for healthy and sustainable buildings? E3S Web Conf. 2024;523:03005.

United States Environmental Protection Agency. National ambient air quality standards for ozone. Fed Regist. 2015;80(206):65292-375.

Clinical and Laboratory Standards Institute. Performance standards for antimicrobial susceptibility testing. 33rd ed. CLSI supplement M100. Wayne, PA: Clinical and Laboratory Standards Institute; 2023. 352 p.

Zembower TR. Epidemiology of infections in cancer patients. Cancer Treat Res. 2014;161:43-89.

Kowalski WJ, Bahnfleth WP, Whittam TS. Filtration of airborne microorganisms: modeling and prediction. ASHRAE Trans. 1999;105:1-17.

Moreau M, Orange N, Feuilloley MG. Non-thermal plasma technologies: new tools for bio-decontamination. Biotechnol Adv. 2008;26(6):610-7.

Laroussi M. Low temperature plasma-based sterilization: overview and state-of-the-art. Plasma Process Polym. 2005;2(5):391-400.

Morawska L, Cao J. Airborne transmission of SARS-CoV-2: the world should face the reality. Environ Int. 2020;139:105730.

Douwes J, Thorne P, Pearce N, Heederik D. Bioaerosol health effects and exposure assessment: progress and prospects. Ann Occup Hyg. 2003;47(3):187-200.

Tang JW, Li Y, Eames I, Chan PK, Ridgway GL. Factors involved in the aerosol transmission of infection and control of ventilation in healthcare premises. J Hosp Infect. 2006;64(2):100-14.

Prussin AJ, Marr LC. Sources of airborne microorganisms in the built environment. Microbiome. 2015;3:78.

Chastre J, Fagon JY. Ventilator-associated pneumonia. Am J Respir Crit Care Med. 2002;165(7):867-903.

Church D, Elsayed S, Reid O, Winston B, Lindsay R. Burn wound infections. Clin Microbiol Rev. 2006;19(2):403-34.

Graves DB. The emerging role of reactive oxygen and nitrogen species in redox biology and some implications for plasma applications to medicine and biology. J Phys D Appl Phys. 2012;45(26):263001.

Somsen GA, van Rijn C, Kooij S, Bem RA, Bonn D. Small droplet aerosols in poorly ventilated spaces and SARS-CoV-2 transmission. Lancet Respir Med. 2020;8(7):658-9.

Adams RI, Miletto M, Taylor JW, Bruns TD. Dispersal in microbes: fungi in indoor air are dominated by outdoor air and show dispersal limitation at short distances. ISME J. 2013;7(7):1262-73.

Oliver JD. Recent findings on the viable but nonculturable state in pathogenic bacteria. FEMS Microbiol Rev. 2010;34(4):415-25.

Nocker A, Cheung CY, Camper AK. Comparison of propidium monoazide with ethidium monoazide for differentiation of live vs. dead bacteria by selective removal of DNA from dead cells. J Microbiol Methods. 2006;67(2):310-20.

Cox J, Moyer P, Furlan R, Reineke L, Woods K, Castronovo D. Indoor air quality in healthcare facilities: a comprehensive review. J Hosp Infect. 2022;126:1-12.

Clarridge JE. Impact of 16S rRNA gene sequence analysis for identification of bacteria on clinical microbiology and infectious diseases. Clin Microbiol Rev. 2004;17(4):840-62

Downloads

Received

2026-07-01

Accepted

2026-11-09

Published

2026-12-04

How to Cite

Ibrahim Saeed, M., Luay Osman, A., Alamin Altoum, A., Omar Hussein, S.-E., & Elnour, S. (2026). An Improved Protocol for Indoor Airborne Bacterial Enumeration and Elimination Using a Cold- Plasma Air Sanitizer: A pilot study. International Journal of Applied Technology in Medical Sciences, 5(2), 4-12. https://doi.org/10.54878/r2x84577